Three Phase Liquid-Filled Pad Mounted Distribution Transformer

A liquid-filled three-phase pad mounted distribution transformer designed for commercial, industrial, institutional, and utility-related medium-voltage distribution applications. Available configurations vary by rated capacity, primary voltage, secondary voltage, accessories, and project requirements.

Green three-phase pad-mounted distribution transformer with front access cabinet doors and external radiator cooling section

Product Specifications

Technical specifications
Product TypeThree Phase Liquid-Filled Pad Mounted Distribution Transformer
PhaseThree Phase
Rated Capacity75 kVA to 2,500 kVA
Typical Capacity Options
  • 75 kVA
  • 112.5 kVA
  • 150 kVA
  • 225 kVA
  • 300 kVA
  • 500 kVA
  • 750 kVA
  • 1,000 kVA
  • 1,500 kVA
  • 2,000 kVA
  • 2,500 kVA
Typical High-Voltage Configurations
  • 7,620 V
  • 7,957 V
  • 12,470 V
  • 13,200 V
  • 13,800 V
  • 19,920 V
  • 34,500 V
  • Other configurations available upon request
Typical Low-Voltage Configurations
  • 240 V
  • 480 V
  • 480Y/277 V
  • 600Y/347 V
  • Other configurations available upon request
Installation TypePad Mounted
Insulation / Cooling TypeLiquid-Filled
Typical Applications
  • Commercial buildings
  • Industrial facilities
  • Utility-related distribution systems
  • Institutional facilities
  • Project-based medium-voltage distribution
Available features and configuration options may include
  • Compact enclosed construction
  • Multiple capacity and voltage configurations
  • Reliable distribution performance
  • Low-loss design options
  • Outdoor or project-specific installation
  • Configurable accessories and connections

Specifications may vary by model and project. Final ratings, dimensions, accessories, fluid type, and electrical configuration will be confirmed in the commercial quotation and technical documentation.

Request a Quote

Technical Data

Rated Capacity and Loss Data

Typical rated capacities with corresponding no-load and on-load loss values. High-voltage and low-voltage configurations apply across the listed capacity range.

Three phase pad mounted transformer rated capacity, voltage, and loss data
Rated Capacity (kVA)High Voltage (V)Low Voltage (V)Loss (W)
No-load Loss (W)On-load Loss (W)
7534,500
19,920
13,800
13,200
12,470
7,957
7,620
or others
240
480
480Y/277
600Y/347
1801,250
112.52001,500
1502802,200
2254003,050
3004803,650
5006805,100
7509807,500
1,0001,15010,300
1,5001,64014,500
2,0002,16020,645
2,5002,68027,786

Loss values are typical reference figures. Guaranteed values are confirmed in the written quotation and technical documentation for each project.

The specifications and performance data shown on this page represent typical or available product configurations. Final capacity, voltage, loss values, dimensions, accessories, insulation fluid, connections, and other technical specifications are subject to model selection and written confirmation.