Products
Three Phase Liquid-Filled Pad Mounted Distribution Transformer
A liquid-filled three-phase pad mounted distribution transformer designed for commercial, industrial, institutional, and utility-related medium-voltage distribution applications. Available configurations vary by rated capacity, primary voltage, secondary voltage, accessories, and project requirements.

Product Specifications
| Product Type | Three Phase Liquid-Filled Pad Mounted Distribution Transformer |
|---|---|
| Phase | Three Phase |
| Rated Capacity | 75 kVA to 2,500 kVA |
| Typical Capacity Options |
|
| Typical High-Voltage Configurations |
|
| Typical Low-Voltage Configurations |
|
| Installation Type | Pad Mounted |
| Insulation / Cooling Type | Liquid-Filled |
| Typical Applications |
|
| Available features and configuration options may include |
|
Specifications may vary by model and project. Final ratings, dimensions, accessories, fluid type, and electrical configuration will be confirmed in the commercial quotation and technical documentation.
Request a QuoteTechnical Data
Rated Capacity and Loss Data
Typical rated capacities with corresponding no-load and on-load loss values. High-voltage and low-voltage configurations apply across the listed capacity range.
| Rated Capacity (kVA) | High Voltage (V) | Low Voltage (V) | Loss (W) | |
|---|---|---|---|---|
| No-load Loss (W) | On-load Loss (W) | |||
| 75 | 34,500 19,920 13,800 13,200 12,470 7,957 7,620 or others | 240 480 480Y/277 600Y/347 | 180 | 1,250 |
| 112.5 | 200 | 1,500 | ||
| 150 | 280 | 2,200 | ||
| 225 | 400 | 3,050 | ||
| 300 | 480 | 3,650 | ||
| 500 | 680 | 5,100 | ||
| 750 | 980 | 7,500 | ||
| 1,000 | 1,150 | 10,300 | ||
| 1,500 | 1,640 | 14,500 | ||
| 2,000 | 2,160 | 20,645 | ||
| 2,500 | 2,680 | 27,786 | ||
Loss values are typical reference figures. Guaranteed values are confirmed in the written quotation and technical documentation for each project.
The specifications and performance data shown on this page represent typical or available product configurations. Final capacity, voltage, loss values, dimensions, accessories, insulation fluid, connections, and other technical specifications are subject to model selection and written confirmation.